| Technical Data |
|
| Design |
Angular |
| Based on standard |
EN 60947-5-2VDI/VDE 3845 |
| Approval |
RCM trademarkc UL us (OL) |
| CE mark (see declaration of conformity) |
To EU EMC DirectiveIn accordance with EU RoHS Directive |
| UKCA marking (see declaration of conformity) |
To UK instructions for EMCTo UK RoHS instructions |
| KC mark |
KC-EMV |
| Note on materials |
RoHS-compliant |
| Measuring principle |
Inductive |
| Ambient temperature |
-2570 |
| Switching output |
AS-Interface |
| Switching element function |
N/C or N/O contact, switchable |
| Max. switching frequency |
100 |
| Max. switching output voltage DC |
26.4 |
| Max. output current DC |
100 |
| Max. switching capacity DC |
2.5 |
| Protocol |
AS-Interface |
| AS-Interface, Protocol version |
V3.0 |
| AS-Interface, Adressing range |
1A ... 31A (0)1B ... 31B |
| AS-Interface, Product identification |
IO code: DID code: AID1 code: 7ID2 code: E |
| Operational voltage range DC |
26.531.6 |
| No-load supply current |
35 |
| Electrical connection input |
M12x1 |
| Electrical connection 1, connection type |
Plug and socket strip |
| Electrical connection 1, cable outlet |
Straight |
| Electrical connection 1, design |
Round |
| Electrical connection 1, connector system |
M12x1, A-coded to EN 61076-2-101 |
| Electrical connection 1, number of connections/cores |
4 |
| Electrical connection 1, connection pattern |
00995599 |
| Type of mounting |
Threaded |
| Mounting position |
optional |
| Product weight |
70 |
| Material housing |
PBT |
| Material screws |
High-alloy stainless steel |
| Material fitting |
Nickel-plated, die-cast zinc |
| Ready status indication |
Green LED |
| Switching status indication |
Yellow LED |
| Status indication |
LED yellow = valve switching statusLED red = wire break/short circuit at valve |
| Storage temperature |
-2570 |
| Degree of protection |
IP67 |
| Shock resistance |
Shock test with severity level 2 to FN 942017-5 and EN 60068-2-27 |
| Vibration resistance |
Transport application test with severity level 2 to FN 942017-4 and EN 60068-2-6 |
| LABS (PWIS) conformity |
VDMA24364 zone III |
| Pollution degree |
3 |