| Technical Data |
|
| Design |
Digital, electropneumatic positioner |
| Mode of operation |
Single-acting |
| Design characteristics |
Safety pneumatic output 2 exhausted |
| Mounting position |
optional |
| Type of mounting |
With accessoriesTo VDI/VDE 3845 |
| Functional principle of measuring system |
Potentiometer |
| Sensing range |
0115 |
| Display |
LCD display, via software 90° rotatable |
| Setting options |
Via display and keys |
| Cycle time |
20 |
| Nominal altitude of use |
<= 2000 m NHN |
| Overvoltage category |
II |
| Operating pressure |
20.3116 |
| Operating medium |
Compressed air to ISO 8573-1:2010 [7:4:4] |
| Note on operating and pilot medium |
Lubricated operation not possibleMaximum particle size 40 µm |
| Air flow rate at Δp = 6 bar |
380 |
| Pneumatic connection |
G1/4 |
| Reverse polarity protection |
yes |
| Connection resistance |
380 |
| digital input, signal range |
4 - 20 mA with HART |
| Analogue inputs, input impedance |
480 ohm at 20 mA |
| Analog inputs, overload protection |
<65 mA |
| Analogue inputs, electrical isolation |
yes |
| Characteristic for inputs |
1x to IEC 61131-2, type 3 |
| Digital inputs, reverse polarity protection |
yes |
| Digital inputs, electrical isolation |
yes |
| Digital inputs, overload protection |
33 V |
| Electrical connection 1, function |
Analogue inputDigital inputExternal path/angle sensor |
| Electrical connection 1, connection type |
Terminal strip |
| Electrical connection 1, connector system |
Spring-loaded terminal |
| Electrical connection 1, number of connections/cores |
7 |
| Cable fitting |
2x M20x1.5 |
| Max. cable length |
30 m for external position sensorShielded |
| Ambient temperature |
-4080 |
| Note on ambient temperature |
Display: -30 - 80°C |
| Storage temperature |
-4080 |
| Climatic category |
1K5 to EN 60721 for storage4K3 to EN 60721 for operation |
| Degree of protection |
IP66IP67 |
| Shock resistance |
Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27 |
| Vibration resistance |
Transport application test with severity level 2 to FN 942017-4 and EN 60068-2-6 |
| Pollution degree |
3 |
| Approval |
RCM trademark |
| CE mark (see declaration of conformity) |
To EU EMC DirectiveTo EU Explosion Protection Directive (ATEX)In accordance with EU RoHS Directive |
| UKCA marking (see declaration of conformity) |
To UK instructions for EMCTo UK RoHS instructions |
| Material housing |
Aluminium, powder-coated |
| Material screen |
PC |
| Material shaft |
High-alloy stainless steel |
| Material coupling |
High-alloy stainless steel |
| Material screws |
Galvanised steel |
| Material seals |
EPDMNBRVMQ |
| LABS (PWIS) conformity |
VDMA24364 zone III |
| Note on materials |
RoHS-compliant |
| Product weight |
2640 |