Найти
Телефон
Меню

Официальный представитель завода АО «Таурас-Феникс»

в Уфе, в Казани, в Оренбурге, в Перми, в Ижевске и в Казахстане

Taures-fenix
+7 347 201 77 10 Бесплатно по России

DP1223 – фото
DP1223 – фото
DP1223 – фото
Фото
Видео

На DP1223

Для заявки пишите в WhatsApp или Telegram

# #

Характеристики

Product designation Converter IO-Link - 0...10 V

Все характеристики

Number of inputs and outputs Number of analog outputs: 2
Communication interface IO-Link
Operating voltage 18...30 DC; (to SELV/PELV)
Nominal voltage DC 24
Current consumption 300
Max. current load total 0.2
Number of inputs and outputs Number of analog outputs: 2
Number of analog outputs 2
Analog voltage output 0...10
Min. load resistance 3000
Precision analog output 0,25
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
Profiles
Common - I&DIdentification and Diagnosis
SIO mode no
Required master port class A/B
Process data analog 2
Min. process cycle time 3.6
IO-Link process data (cyclical)
Functionbit length
device status4
voltage - output 116
voltage - output 216
IO-Link functions (acyclical) application specific tag
Supported DeviceIDs
Type of operationDeviceID
default614
Ambient temperature -25...70
Note on ambient temperature
2000 m: -25...70 °C
3000 m: -25...64 °C
4000 m: -25...62 °C
Storage temperature -25...70
Max. relative air humidity 90; (linearly decreasing to 50 % (40 °C) non condensing)
Max. height above sea level 4000
Protection IP 67
Degree of soiling 2
MTTF 432
UL approval
Tamax. 55 °C
File number ULE205959
Weight 91
Housing rectangular
Dimensions 63 x 30 x 24
Material housing: PA
Display
Power1 x LED, green
analog output2 x LED, yellow
Accessories (optional)
mounting clip
Remarks
Further information is available in the manual.
the device complies with overvoltage category II
Pack quantity 1 pcs.

Приемущества

Easy setting of the output voltage via cyclical IO-Link process values
Two analog outputs controllable via IO-Link
Digital transmission eliminates the risk of EMC interference
Signal conversion of IO-Link into analog signals