| Number of inputs and outputs |
Number of digital outputs: 2; Number of analog outputs: 1 |
| Measuring range |
| 5...300 l/min | 0.3...18 m³/h |
|
| Process connection |
threaded connection G 2 external thread DN50 flat seal |
| System |
gold-plated contacts |
| Application |
Totalizer function; empty pipe detection; for industrial applications |
| Installation |
connection to pipe by means of an adapter |
| Media |
Conductive liquids; water; water-based media |
| Note on media |
| conductivity: ≥ 20 µS/cm | | viscosity: < 70 mm²/s (40 °C) |
|
| Medium temperature |
-10...90 |
| Pressure rating |
|
| MAWP (for applications according to CRN) |
|
| Operating voltage |
18...32 DC; (to SELV/PELV) |
| Current consumption |
< 150 |
| Protection class |
III |
| Reverse polarity protection |
yes |
| Power-on delay time |
5 |
| Measuring principle |
magnetic-inductive |
| Number of inputs and outputs |
Number of digital outputs: 2; Number of analog outputs: 1 |
| Inputs |
counter reset |
| Total number of outputs |
2 |
| Output signal |
switching signal; analog signal; pulse signal; frequency signal; IO-Link; (configurable) |
| Electrical design |
PNP/NPN |
| Number of digital outputs |
2 |
| Output function |
normally open / closed; (configurable) |
| Max. voltage drop switching output DC |
2 |
| Permanent current rating of switching output DC |
250; (per output) |
| Number of analog outputs |
1 |
| Analog current output |
4...20; (scalable) |
| Max. load |
500 |
| Analog voltage output |
0...10; (scalable) |
| Min. load resistance |
2000 |
| Pulse output |
flow rate meter |
| Short-circuit protection |
yes |
| Type of short-circuit protection |
yes (non-latching) |
| Overload protection |
yes |
| Frequency of the output |
0.1...10000 |
| Measuring range |
| 5...300 l/min | 0.3...18 m³/h |
|
| Display range |
| -360...360 l/min | -21.6...21.6 m³/h |
|
| Resolution |
|
| Set point SP |
| 6.5...300 l/min | 0.4...18 m³/h |
|
| Reset point rP |
| 5...298.5 l/min | 0.3...17.9 m³/h |
|
| Analog start point ASP |
| 0...240 l/min | 0...14.4 m³/h |
|
| Analog end point AEP |
| 60...300 l/min | 3.6...18 m³/h |
|
| Low flow cut-off LFC |
|
| In steps of |
|
| Measuring dynamics |
1:60 |
| Pulse value |
0.0001...300 x 10³ m³ |
| In steps of |
0.0001 m³ |
| Pulse length |
0,016...2 |
| Dynamic response T05 / T09 |
T09 = 3 (Q > 15 l/min) |
| Response time |
0.35; (dAP = 0) |
| Delay time programmable dS, dr |
0...50 |
| Damping process value dAP |
0...5 |
| Parameter setting options |
Flow monitoring; quantity meter; Preset counter; Temperature monitoring; hysteresis / window; normally open / closed; switching logic; current/voltage/frequency/pulse output; Start-up delay; display can be deactivated; Display unit; empty pipe detection |
| Communication interface |
IO-Link |
| Transmission type |
COM2 (38,4 kBaud) |
| IO-Link revision |
1.1 |
| SDCI standard |
IEC 61131-9 CDV |
| Profiles |
| Smart Sensor - SSP 0 | Generic Profiled Sensor | | Function | Device identification | | Function | Process data variable |
|
| SIO mode |
yes |
| Required master port class |
A |
| Process data analog |
3 |
| Process data binary |
2 |
| Min. process cycle time |
5 |
| Supported DeviceIDs |
| Type of operation | DeviceID |
|---|
| default | 391 |
|
| Ambient temperature |
-10...60 |
| Storage temperature |
-25...80 |
| Protection |
IP 65; IP 67 |
| EMC |
|
| CPA approval |
| model number | 004MI | | accuracy class | - | | maximum allowable error | ± 1,5 % FS | | Q (min) | 0,3 m³/h | | Q (t) | - | | Q (max) | 18 m³/h | | Medium temperature | -10...70°C |
|
| Shock resistance |
| DIN EN 60068-2-27 | 20 g (11 ms) |
|
| Vibration resistance |
| DIN EN 60068-2-6 | 5 g (10...2000 Hz) |
|
| MTTF |
85 |
| UL approval |
| UL approval number | I008 | | File number UL | E174189 |
|
| Pressure equipment directive |
sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| Weight |
3176 |
| Housing |
rectangular |
| Dimensions |
200 x 103 x 117 |
| Material |
stainless steel (1.4404 / 316L); stainless steel (1.4571/316Ti ); PEI; FKM; PBT-GF20; TPE-U |
| Materials (wetted parts) |
Pipe section: stainless steel (1.4404 / 316L); Process connection sealing: NBR fiber-reinforced Gasket; FKM; stainless steel (1.4571/316Ti ); PEEK |
| Process connection |
threaded connection G 2 external thread DN50 flat seal |
| Display |
| Display unit | 6 x LED, green (l/min, m³/h, l, m³, 10³, °C) | | Switching status | 2 x LED, yellow | | Measured values | alphanumeric display, 4-digit | | Programming | alphanumeric display, 4-digit |
|
| Items supplied |
| sealings: 2, Centellen | | Label |
|
| Remarks |
| MW = Measured value | | MEW = Final value of the measuring range |
|
| Pack quantity |
1 pcs. |
| Connection |
Connector: 1 x M12; coding: A; Contacts: gold-plated |