Характеристики

Protection IP 65, IP 67
Approval CE, cULus, CRN, UKCA, DNV, Korea Registered

Все характеристики

Number of inputs and outputs Number of digital outputs: 2; Number of analog outputs: 1
Measuring range
0.8...250 l/min0.3...82.9 m/s0.05...15 m³/h
Process connection threaded connection G 1/4 Internal thread DN8
Application for industrial applications
Media Argon (Ar); carbon dioxide (CO2); nitrogen (N2); compressed air
Medium temperature -10...60
Min. bursting pressure
64 bar6.4 MPa
Pressure rating
16 bar1.6 MPa
MAWP (for applications according to CRN) 9.5
Operating voltage 18...30 DC; (to SELV/PELV)
Current consumption < 80
Protection class III
Reverse polarity protection yes
Power-on delay time 1
Number of inputs and outputs Number of digital outputs: 2; Number of analog outputs: 1
Inputs counter reset
Output signal switching signal; analog signal; pulse signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / closed; (configurable)
Max. voltage drop switching output DC 2.5
Permanent current rating of switching output DC 150; (per output)
Number of analog outputs 1
Analog current output 4...20; (scalable)
Max. load 500
Pulse output consumed quantity meter
Short-circuit protection yes
Type of short-circuit protection yes (non-latching)
Overload protection yes
Measuring range
0.8...250 l/min0.3...82.9 m/s0.05...15 m³/h
Display range
0...300 l/min0...99.5 m/s0...18 m³/h
Resolution
0.2 l/min0.1 m/s0.01 m³/h
Set point SP
2.2...249.9 l/min0.7...82.9 m/s0.13...14.99 m³/h
Reset point rP
0.9...248.7 l/min0.3...82.5 m/s0.06...14.92 m³/h
Analog start point ASP
0...200 l/min0...66.3 m/s0...12 m³/h
Analog end point AEP
50...250 l/min16.6...82.9 m/s3...15 m³/h
Low flow cut-off LFC
0.3...2.7 l/min0.1...0.9 m/s0.02...0.16 m³/h
In steps of
0.1 l/min0.1 m/s0.01 m³/h
Response time 0.05
Measuring range
0...100000000 m³0...353146667.2 scf
Display range
0...100000000 m³0...353146667.2 scf
Set point SP
0.001...10000000 m³0.05...353146667.2 scf
Pulse value
0.001...10000000 m³0.05...353146667.2 scf
In steps of
0.0001 m³0.005 scf
Pulse length 0.01...2
Dynamic response T05 / T09 T09 = 0,5
Temperature coefficient ± 0,07 % MW
Accuracy (in the measuring range) ± (6 % MW + 0,6 % MEW); at medium temperature 23 °C
Repeatability ± (0,4 % MW + 0,1 % MEW)
Response time 0.1; (dAP = 0)
Damping process value dAP 0...5
Parameter setting options hysteresis / window; normally open / closed; current/pulse output; display can be rotated and switched off; Display unit; totalizer
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9 CDV
Profiles
Common - I&DIdentification and Diagnosis
FunctionMeasurement data, standard resolution
SIO mode yes
Required master port class A
Process data analog 8
Process data binary 2
Min. process cycle time 7.2
Supported DeviceIDs
Type of operationDeviceID
default861
Ambient temperature 0...60
Storage temperature -20...85
Max. relative air humidity 90
Protection IP 65; IP 67
EMC
DIN EN 60947-5-9
CPA approval
model number003TG
accuracy class-
maximum allowable error± 7 % FS
Q (min)0,05 m³/h (Air)
Q (t)-
Q (max)15 m³/h (Air)
Vibration resistance
DIN EN 68000-2-65 g (10...2000 Hz)
MTTF 183
UL approval
UL approval numberI012
File number ULE174189
Pressure equipment directive sound engineering practice; can be used for stable gases fluid group 2
Weight 558
Housing rectangular
Dimensions 182 x 45.4 x 67.8
Material PBT+PC-GF30; PPS GF40; stainless steel (1.4301 / 304); stainless steel (1.4305 / 303); steel (1.5523) galvanized; 2.0401 (brass / CW614N); FKM
Materials (wetted parts) EN AW-6082 (aluminium); stainless steel (1.4305 / 303); FKM; ceramics glass passivated; PPS GF40; Al2O3 (ceramics); acrylate
Process connection threaded connection G 1/4 Internal thread DN8
Display
Color display 1,44", 128 x 128 pixels
2 x LED, yellow
Remarks
MW = Measured value
MEW = Final value of the measuring range
Standard conditions: 1013.25 mbar / 15 °C / 0 % relative humidity
For information about installation and operation please see the operating instructions.
Pack quantity 1 pcs.
Connection Connector: 1 x M12; coding: A

Приемущества

Precise measurement of flow, consumption, pressure and medium temperature
High accuracy, repeatability and measurement dynamics
For detecting argon (Ar), carbon dioxide (CO2), nitrogen (N2) and compressed air
Red/green display for clear identification of the acceptable range
Display can be rotated for optimum alignment
Convenient operation via buttons or parameter setting via IO-Link