| Product characteristics |
|
| Number of inputs and outputs |
Number of analog outputs: 1 |
| Measuring range |
<table><tr><td>-50...300 °C</td><td>-58...572 °F</td></tr></table> |
| Communication interface |
IO-Link |
| Application |
|
| System |
gold-plated contacts |
| Application |
for Pt100 and Pt1000 measuring elements |
| Electrical data |
|
| Operating voltage |
20...32 DC |
| Protection class |
III |
| Reverse polarity protection |
yes |
| Power-on delay time |
1 |
| Integrated watchdog |
yes |
| Inputs / outputs |
|
| Number of inputs and outputs |
Number of analog outputs: 1 |
| Outputs |
|
| Total number of outputs |
1 |
| Output signal |
analog signal; IO-Link; (configurable) |
| Number of analog outputs |
1 |
| Analog current output |
4...20 |
| Max. load |
300 |
| Short-circuit protection |
yes |
| Type of short-circuit protection |
yes (non-latching) |
| Overload protection |
yes |
| Measuring/setting range |
|
| Measuring range |
<table><tr><td>-50...300 °C</td><td>-58...572 °F</td></tr></table> |
| Factory setting |
-50...300 °C |
| Accuracy / deviations |
|
| Precision analog output |
± 0,3 + (± 0,1 % MS) |
| Temperature coefficient |
0,1 |
| Reaction times |
|
| Max. measuring/display cycle |
100 |
| Interfaces |
|
| Communication interface |
IO-Link |
| Transmission type |
COM2 (38,4 kBaud) |
| IO-Link revision |
1.0 |
| Min. process cycle time |
2.3 |
| Supported DeviceIDs |
<table><tr><th>Type of operation</th><th>DeviceID</th></tr><tr><td>default</td><td>141</td></tr></table> |
| Operating conditions |
|
| Ambient temperature |
-25...70 |
| Storage temperature |
-40...85 |
| Protection |
IP 67 |
| Tests / approvals |
|
| EMC |
<table><tr><td>EN 61326-1</td><td></td></tr></table> |
| Shock resistance |
<table><tr><td>DIN IEC 68-2-27</td><td>50 g (11 ms)</td></tr></table> |
| Vibration resistance |
<table><tr><td>DIN IEC 68-2-6</td><td>20 g (10...2000 Hz)</td></tr></table> |
| MTTF |
449 |
| Mechanical data |
|
| Weight |
40.5 |
| Housing |
rectangular |
| Dimensions |
52 x 25 x 18 |
| Material |
PA; PET |
| Sealing material |
FKM |
| Remarks |
|
| Remarks |
<table><tr><td> cULus - Class 2 source required</td></tr><tr><td>MS = set measuring span</td></tr></table> |
| Pack quantity |
1 pcs. |
| Electrical connection |
|
| Connection |
Connector: 1 x M12; coding: A; Moulded body: TPU (urethane); Locking: stainless steel (1.4404 / 316L); sealing: FKM; Contacts: gold-plated |